Abstract

Low-voltage ride-through (LVRT) strategies for grid-forming converters typically rely on explicit current limiting to prevent overcurrents during voltage dips. In doubly-fed induction generator (DFIG) wind turbines, rotor-side converters are commonly oversized to accommodate transient free-flux dynamics, enabling simpler control solutions. This paper proposes a simplified LVRT scheme for rotor-flux-oriented grid-forming DFIG control based on a supervisory modification of the outer-loop power references. During voltage dips, positive-sequence active current is limited while reactive current is prioritized according to grid code requirements, without additional current-limiting structures or control mode switching. The approach preserves grid-forming operation and successfully achieves LVRT while maintaining converter currents within limits across varying grid conditions. However, results show that the LVRT dynamic response strongly depends on grid parameters, characterized by short-circuit ratio (SCR) and grid voltage, due to variations in effective control bandwidth. This dependence makes uniform fault response difficult to guarantee with conventional fixed-parameter PI controllers, suggesting that meeting emerging grid codes may require a shift toward more robust and adaptive grid-forming control strategies.