Effect of Contact Radius and Contact Gap Ratio on Vaccum Arc Characteristics Under High Current Conditions
Abstract
High-voltage vacuum circuit breakers are key switching equipment for power grids. Vacuum arc stability and axial magnetic field (AMF) distribution govern the short-circuit breaking performance and insulation reliability of vacuum interrupters under heavy short-circuit currents. Contact radius (electrode diameter) and gap length are vital structural parameters that jointly adjust the magnetic field, plasma evolution and cooling inside contact gaps, and further dominate high-current arc confinement and extinction. Most existing works only study contact radius or gap separately, lacking quantitative research on their coupling effects and optimal matching strategies for fault current peaks. This paper constructs a steady-state multi-component magnetohydrodynamic (MHD) model for CuCr50 AMF contacts. The model fully covers multi-valence ion ionization/recombination and real cathode emission boundaries. Comparative simulations are carried out at a fixed peak current of 56.56 kA with electrode diameters of $70 \text{mm}, 80 \text{mm}, 90 \text{mm}$ and contact gaps of 10 mm, 15 mm, 20 mm. The axial magnetic field, anode energy flux and effective arc area under various parameter combinations are quantitatively analyzed to summarize the evolution rules of magnetic uniformity and electrode ablation. Relevant optimization suggestions on contact separating motion are put forward based on the simulation results.