Skip to content
Open access

Fault Detection and Location in Distribution Networks with Limited PMU Deployment

Sep 2026 · International Workshop on Applied Measurements for Power Systems · pp. 1-6 · 0 citations · 16 references

Abstract

The growing penetration of distributed energy resources as well as the progressive electrification of critical infrastructures have driven the deployment of Phasor Measurement Units (PMUs) in distribution networks, enabling advanced monitoring and protection applications, although full observability is still not commonly achieved in practice. Among all grid disturbances, fault events introduce several challenges that inherently affect the integrity of the power system. In this regard, this paper presents a fault detection and location method for three-phase distribution networks with limited PMU deployment, based on the assessment of the state estimation residuals. The algorithm evaluates the residual sum of squares in the presence of a fault and, based on this analysis, outputs a connected set of potentially faulted branches. The method relies on a comprehensive model of the possible data acquisition chain, protective instrument transformers feeding P-class PMUs, and is validated through several simulations carried out on the three-phase CIGRE European Medium Voltage distribution network implemented via a Real-Time Digital Simulator (RTDS).

Read PDF

We use cookies to run the site and, with your consent, for analytics and to show ads. See our Cookie Policy.