Diagnostic Study of Geohydrological Actions on Sandcrete Block Wall Structures in Uyo Metropolis, Akwa Ibom State, Nigeria
Abstract
The increasing effect of damping on sandcrete walls often results in walls of structures being defaced and weakened. Therefore, to predict and control water capillaries in cement-sand based structures, it is imperative to delineate site geohydrological conditions. Geoelectrical methods involving vertical electrical sounding (VES) and self-potential (SP) techniques were deployed to determine subsurface resistivity, electrical potential and depth delineated groundwater saturation level at 1.1m, which inferred the likelihood of capillary action from groundwater flux. The SP results were of anti-symmetrical trend, with lower magnitude anomaly corresponding to lower resistivity layers as opposed to the high-magnitude anomaly in high resistivity earth layers. Results further indicate that, 91 building foundations were within low resistivity layers, interpreted to be groundwater saturation layers of which 89 buildings showed evidence of capillary effect, and were diagnosed for not been installed with DPM; while 3buildings within similar earth layers had DPM installed and did not show capillary effect. Whereas 8buildings had their foundations within earth layers delineated with relatively high resistivities and interpreted to be unsaturated groundwater layers, but did not show evidence of capillarity even when DMP were not installed.