Pulse-Type interference suppression based on an improved wavelet threshold for wideband partial discharge detection in transformers

2026 · Research on Engineering Structures and Materials · 0 citations

Abstract

Pulse-type interference at high-voltage (HV) and ultra-high voltage (UHV) transformer sites severely limits the effectiveness of partial discharge (PD) detection, as conventional pulse current measurement below 1 MHz leaves 12-pulse ripple, corona, and electronic switching pulses overlapping with genuine PD signals in both time and frequency domains. This work develops an improved wavelet threshold method tightly integrated with a wideband detection platform featuring a 150 kHz to 60 MHz signal conditioning bandwidth coupled with a 3–50 MHz high-frequency current transformer (HFCT) sensor. A continuously differentiable threshold function with adjustable factor α is constructed to bridge hard and soft thresholding, a layer-dependent adaptive estimator replaces the universal threshold to match noise variance at each decomposition level, and a time-frequency cumulative energy function performs pulse pre-localization before discrimination. Validation on 500 simulation samples, 320 laboratory records from a 220 kV physical platform, and 180 field signals from three substations shows an average SNR gain of 9.3 dB, combined fitness F of 2.38 at 5 dB input SNR (F is a figure of merit balancing noise suppression and waveform preservation), and laboratory identification rates of 95.2%, 93.6%, and 94.3% for the three interference categories. Pooled field detection accuracy reaches 93.7%, feature-parameter recovery errors stay within 8.1%, and single-record processing settles at 52 ms. Pilot deployments reduced the detection blind zone from 6%–8% down to 2.5%–3%. These findings demonstrate the practical value of the proposed method for improving the reliability of online insulation condition assessment in harsh substation environments.

Read PDF

Similar papers

Open access 2026

Dual-sensor correlation for wideband HFCT partial discharge detection and interference suppression in transformers

On-site partial discharge (PD) detection of power transformers is challenged by strong electromagnetic interferences, including converter pulsation, corona, and power-side harmonics, whose spectra overlap with PD signals. A dual-channel synchronous detection system based on self-developed wideband high-frequency curren...

Guang-Hu Xu, Zhong-Qiang Zhan, Dan-Dong He et al. · 0 citations
Conference Sep 2026

Research and Application of Peak Detector Circuits for Online Partial Discharge Monitoring

Partial Discharge (PD) is a primary indicator of insulation degradation in high-voltage power equipment, and its application in online monitoring is critical for predictive maintenance. PD events are characterized by their ultra-short pulse and wide spectral bandwidth. While peak detector circuits are widely utilized t...

Keng-Wei Liang, Chang-Hsing Lee, Ta-Lun Lo et al. · 0 citations
Review Open access Oct 2026

A Review of Insulation Stress and Partial Dischargein Medium-Frequency Transformers Under Fast Repetitive Voltage Pulses

The use of wide-bandgap power devices in solid-state transformers enables higher switching frequencies and power densities, but it also exposes medium-frequency transformer insulation to fast repetitive voltage pulses. Short rise times, high dv/dt, high repetition frequencies, and harmonic content can produce nonunifor...

Xin-Yue Wo · 0 citations
Open access Sep 2026

Algorithm for processing transient signals for detection and analysis of partial discharges and insulation condition diagnostics

RELEVANCE of the study lies in the need to improve the reliability of medium-voltage distribution networks and the implementation of advanced insulation condition diagnostics based on the analysis of transient process signals (TPS). THE PURPOSE. To develop an algorithm for automatic detection and filtering of partial...

I. Minaev, R. Khuziashev · 0 citations
Open access 2026

TEV Signal Analysis in Power Transformers: Effects of PD Location and Resonance Modes

Detection of partial discharge (PD) in power transformers is crucial since it indicates early-stage insulation degradation that may lead to system failure. The transient earth voltage (TEV) sensor offers a non-intrusive method for measuring PD during online transformer operation. In this paper, the application of the T...

Mahdi Abbasi, M. Lachance, Éric David · 0 citations
Open access Sep 2026

Harmonic Disturbance Identification and Suppression Method Under Compound Power Quality Disturbance

High photovoltaic penetration introduces coupled power-quality disturbances whose overlapping RMS, harmonic, and transient signatures are difficult to distinguish under noise. This study develops a field-calibrated diagnosis-and-mitigation workflow for distributed photovoltaic systems. A balanced 17-class dataset is sy...

Zhi-Quan Liu, Jun Su, Chao-Long Tang et al. · 0 citations