Sep 2026· Frontiers in Energy Research· 0 citations· 23 references
Abstract
Virtual synchronous generator (VSG) is prone to transient power angle instability under grid fault, which weakens its voltage and frequency support ability to the grid. During the grid fault, the evolution characteristics of VSG transient power angle and terminal voltage are closely coupled with the grid fault voltage. Using the VSG terminal voltage to sense the grid fault information, the active control of VSG transient power angle under different fault depths can be realized without detecting the grid voltage. Therefore, this paper first analyzes the transient power angle characteristics of VSG and the transient characteristics of terminal voltage, analyzes the mapping relationship between them and the grid fault voltage, and establishes the terminal voltage information perception mechanism. Based on this, an adaptive control framework for VSG transient power angle is constructed. The active power command value is dynamically adjusted by using the terminal voltage sensing information to reduce the imbalance of VSG active power input and output during the fault period. Furthermore, a control parameter tuning method based on terminal voltage sensing information is proposed to ensure the transient stable operation of VSG under different fault depths. Finally, the correctness of the theoretical analysis and the effectiveness of the proposed method are verified by simulation and experiment.
The virtual synchronous generator (VSG) is an effective grid-forming control technique for power converters that are required to provide inertia, frequency support, and voltage support. This work focuses on balanced three-phase operation under symmetrical voltage sags, where a three-phase grid-forming converter may sim...
Jia-Wei Liu, Cheng-Bo Zhang, Qi Wang et al.· Energies· 0 citations
Deep grid-voltage depressions may simultaneously induce transient power-angle instability and excessive fault current in VSGs, thereby compromising the operational security of grid-connected converters. To address this coupled challenge, an active-power deviation and angle-feedback compensation (APDAFC) strategy is dev...
A fixed-proportion load shedding scheme with fixed-parameter reactive power compensation can barely maintain voltage under weak disturbances. Once the output of new energy sources fluctuates drastically, the adaptive matching control strategy cannot be implemented, resulting in poor transient voltage control stability...
Yun-Ling Sun, Hua-Long Li, Xin-Ke Hang et al.· Journal of Physics, Conferen...· 0 citations
When the modular multilevel converter is connected to the grid, the voltage reference command issued by the dispatching system to the MMC is updated at 15-min intervals, but the rapid fluctuation of the DC side power can be close to a few seconds. This kind of phenomenon leads to the mismatch of time scale between th...
As renewable generation and power-electronic interfaces account for a growing share of power systems, reduced system inertia and weakened voltage support place greater demands on the stable operation of weak and passive networks. This paper proposes a virtual synchronous generator (VSG)-based active support strategy fo...
Wei Chen, Yun-Che Su, Fang Liu et al.· Symmetry· 0 citations