Sep 2026· International Conference on Intelligent Transportation Systems and Automation Control· Vol 14368, pp. 143681J - 143681J-10· 0 citations· 15 references
Engineering
TL;DR
The results indicate that cloud-edge collaboration can support reliable fault diagnosis and location in networked distribution automation without continuous raw-waveform upload.
Abstract
Networked automation systems require fault-diagnosis functions that are fast enough for local control while still maintaining global model consistency. This paper repackages distribution-feeder fault location as a low-latency cloud-edge automation problem. The edge layer performs event triggering, phasor-sequence feature compression, topology-masked graph neural network (GNN) inference, and first-response section ranking. The cloud layer maintains a digital-twin feeder model, verifies low-confidence cases, and distributes calibrated model updates to field gateways. A confidence-aware split strategy is developed so that routine faults are processed on the edge fast path, whereas difficult topology and distributed energy resource (DER) cases are selectively escalated to the cloud. A case study on a modified Institute of Electrical and Electronics Engineers (IEEE) 33-bus active feeder shows 98.4% section-level accuracy, 0.21-km mean distance error, 118-ms median decision latency, and 31.5-kB uplink payload per event under mixed DER, fault-resistance, and topology-switching scenarios. The results indicate that cloud-edge collaboration can support reliable fault diagnosis and location in networked distribution automation without continuous raw-waveform upload. The same cloud-edge automation framework can also incorporate optical-fiber sensing, infrared inspection, or camera- or light detection and ranging (LiDAR)-based field inspection streams when distribution assets are monitored by optical sensing infrastructure.
High penetrations of distributed energy resources require energy regulation that combines cloud-level global optimization with edge-level fast response. This paper proposes EC-HDT, a device-edge-cloud hierarchical digital twin in which a lightweight graph-attention-temporal-convolution estimator reconstructs local stat...
The results show that cloud-edge intelligence can support continuous online monitoring, rapid abnormal-state diagnosis, and reliability-oriented automation of critical distribution infrastructure.
Hong Wu, Chen Xu, Xin-Yu Ma et al.· International Conference on...· 0 citations
A latency-aware reliability analysis method for 5G-enabled distribution automation that supports optical-inspection-assisted automation scenarios in which camera, LiDAR, or thermal records share communication infrastructure with protection commands.
Rui-Tong Yuan, Jun-Ru Han, Jian-Peng Qiu et al.· International Conference on...· 0 citations
Reliable automated control in cloud-native power monitoring requires faults to be traced before stale measurements, delayed alarms, or unsafe commands propagate through optical-fiber Ethernet links and service chains. This study addresses the research problem of locating the initiating field, communication, or software...
Industrial automation is rapidly evolving toward flexible production. This transition requires networks to ensure the deterministic transmission of varying traffic sets across different production stages. Consequently, the system must be capable of rapidly analyzing whether fixed network resources can accommodate all s...
Qi-Ru Chen, Xin-Ping Guan, Lei Xu et al.· IEEE Transactions on Network...· 0 citations